Back to Electrical tools

Breaker Size Calculator

Find the right circuit breaker (OCPD) rating for a load — enter the current directly or let the calculator work it out from kW, voltage and power factor, apply the 125% continuous-load allowance, and get the next standard breaker size up. Everything runs on your device.

Guide: What Size Breaker Do I Need?

Your load

You know the load in
Full-load current16 A

Load type

How does it run?

Continuous loads — water heaters, EV chargers, storage heaters — run at full current for hours, so the breaker is sized at 125% of the load to avoid sitting at its thermal limit.

Breaker rating
20 A
Design current 16 A — next standard IEC size up.
Load current
16 A
Design current
16 A

Now size the cable to match

The cable must carry at least the breaker’s 20 A.

The breaker protects the cable

The cable’s current-carrying capacity must be at least the breaker rating for its installation method and grouping. Motor circuits keep the same rating but use C- or D-curve breakers for the starting surge. Breaking capacity, discrimination and earth-fault protection still need checking against your wiring rules.

Tip: a breaker that nuisance-trips is telling you something — never fit a bigger one on the same cable. Find the overload or fault, or upsize the cable and breaker together.

Questions & answers

Everything you need to understand the breaker size calculator.

How do I work out what size breaker I need?

Find the load’s full-load current — from its nameplate or from kW ÷ (volts × power factor) — then pick the next standard breaker rating above it. For loads that run for hours at a time (heaters, EV chargers, water heaters), size the breaker at 125% of the running current first, so it doesn’t sit near its limit all day. So a 16 A continuous load becomes a 20 A design current and takes a 20 A breaker.

What are the standard breaker sizes?

North American NEC breakers come in 15, 20, 30, 40, 50, 60, 70, 90, 100 A and up (per NEC 240.6); the rest of the world uses the IEC ladder — 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A. The calculator rounds up within a standard breaker series; the sizing logic is the same either way.

Does the cable have to match the breaker?

Yes — this is the rule people miss. The breaker protects the wire, so the wire’s ampacity must be at least the breaker rating, accounting for installation method, grouping and temperature. This is why 14 AWG (2.5 mm²) goes on a 15 A breaker and 12 AWG (4 mm²) on a 20 A. Never upsize a breaker beyond what the existing wire can carry; upsize the wire instead.

What is a continuous load?

A load that runs at or near full current for three hours or more — water heaters, EV chargers, storage heaters, big freezers. Breakers heat up when loaded continuously, so the convention is to load them to no more than 80% — which is the same as sizing the breaker at 125% of the load.

Why does my breaker trip when a motor starts?

Motor starting current can hit 6–8× the running current for a fraction of a second, which trips a fast breaker even though the running load is fine. Motor circuits normally use an inverse-time or HACR-rated breaker (in IEC terms, a C or D curve) of the same rating that rides through the inrush, rather than a bigger breaker.

Does this replace a proper circuit design?

No. Breaker choice also involves the interrupting rating (AIC), coordination with upstream devices, ground-fault protection (GFCI/AFCI where required) and your local wiring rules. Use this to get the rating right, then confirm the full design against the regulations that apply to the installation.

ExequtechOS

Do the whole job in one place

A calculation is just the start. ExequtechOS takes it from estimate to quote, job card, invoice and paid — for your whole team.

Get started with ExequtechOS
  • Turn these numbers into a client-ready quote
  • Job cards, invoicing & inventory in one place
  • Works offline in the field, syncs when you’re back