All guides

How Do I Calculate Voltage Drop? (And Size for a Long Run)

Voltage drop grows with current and distance and shrinks with conductor size. Here is the formula, the limits to design to, and when to go up a gauge.

Voltage Drop Calculator

Enter the current, run length and conductor size for the drop in volts and %, pass or fail.

Every cable has resistance, so it loses a little voltage along its length — and the longer the run and the higher the current, the more it loses. Size a circuit only on ampacity and a long run can arrive with too little voltage to work properly. Voltage drop is the second half of wire sizing.

The formula

Voltage drop = k × I × L × R, where I is the current, L is the one-way run length, and R is the conductor resistance per foot (resistivity ÷ cross-sectional area — so a lower AWG number, a bigger mm², means less drop). The factor k is 2 for DC and single-phase circuits (it counts the return conductor) and √3 for three-phase. Divide the drop by the supply voltage for the percentage.

Enter the one-way route length, not the loop — the ×2 already accounts for the return path.

What drop is acceptable?

The common rule of thumb, and the NEC recommendation, is up to 3% on a branch circuit and 5% total to the furthest point (feeder plus branch). Your local wiring rules set the real limit — design to whatever applies.

Example: a 20 A, 240 V load run 100 ft on 10 AWG (6 mm²) copper drops about 5 V — roughly 2%, comfortably inside the 3% target.

Size and material matter most

Resistance falls as the conductor gets thicker, so going up two AWG sizes (doubling the area) roughly halves the drop. And copper carries current with about a third less resistance than aluminum of the same size, so an aluminum run needs to be a gauge or two larger to match it.

To cut voltage drop…Effect
Up two AWG sizes (2× area)~half the drop
Copper instead of aluminum~⅓ less drop, same size
Halve the run length~half the drop

Voltage Drop Calculator

Enter the supply type, current, run length and conductor size — it returns the drop in volts and %, a pass/fail against your limit, and the voltage left at the load.

When a long run means upsizing

On a long run the ampacity might be fine while the drop fails, so you size up for distance. A circuit that needs 12 AWG for its current may need 10 or 8 AWG once it runs 150 ft — not because the wire would overheat, but because the load would starve. The calculator flags exactly when that switch happens.

This isn’t the whole design

The figures use conductor resistance at a typical operating temperature and ignore reactance, which only matters on large three-phase runs (say 480 V feeders). Always confirm ampacity, protection and installation method against your wiring rules — voltage drop is one check among several.

ExequtechOS

Do the whole job in one place

A calculation is just the start. ExequtechOS takes it from estimate to quote, job card, invoice and paid — for your whole team.

Get started with ExequtechOS
  • Turn these numbers into a client-ready quote
  • Job cards, invoicing & inventory in one place
  • Works offline in the field, syncs when you’re back