All guides

What Size Wire Do I Need? (AWG by Amps)

Two things set wire size: how much current it must carry (ampacity) and how far it runs (voltage drop). Here is the chart, and when to go bigger.

Cable Size & Wire Gauge Calculator

Enter the load, run length and allowed drop for the exact AWG.

Wire size is set by two separate checks, and you use whichever gives the bigger wire:

  • Ampacity — the current the conductor can carry without overheating. This sets the minimum size for the breaker/load.
  • Voltage drop — on a long run, a wire that is thick enough for the current can still lose too much voltage. Long runs get sized up.

Wire size by amps (copper)

For standard copper building wire (60 °C / 75 °C, per NEC 310.16), the common pairings are:

Breaker / loadCopper wireMetric
15 A14 AWG2.5 mm²
20 A12 AWG4 mm²
30 A10 AWG6 mm²
40 A8 AWG10 mm²
50 A6 AWG16 mm²
60 A4 AWG25 mm²
100 A1 AWG / 1/050 mm²

Aluminum carries less current for the same size, so it steps up about two gauges — a circuit that takes 6 AWG copper needs roughly 4 AWG aluminum. It is common on larger feeders and service entrances.

When voltage drop makes you go bigger

A rule of thumb is to keep voltage drop under 3% for a branch circuit. Drop rises with distance and current, so a long run to a shop, well pump or EV charger often needs a size (or two) above the ampacity table. As a feel for it: a 20 A, 240 V circuit on 12 AWG is fine at 50 ft but drifts past 3% out around 100 ft — at which point you go to 10 AWG.

Cable Size & Wire Gauge Calculator

Enter the load, voltage, run length and allowed drop — it returns the exact AWG (or mm²) and the actual drop.

The two checks together

Size for ampacity from the table, then check voltage drop for the run length — and use the larger wire. A short 20 A kitchen circuit is ampacity-limited (12 AWG and done); a long low-voltage or solar-DC run is almost always voltage-drop-limited, where the wire ends up far bigger than the current alone would suggest.

This is a starting point, not the code

Real installations also account for the installation method, insulation temperature rating, how many conductors are bundled together, ambient temperature, and continuous-load derating (size to 125% of a load that runs 3+ hours). Always confirm against the NEC or your local wiring rules, and have an electrician sign off anything you are unsure of.

ExequtechOS

Do the whole job in one place

A calculation is just the start. ExequtechOS takes it from estimate to quote, job card, invoice and paid — for your whole team.

Get started with ExequtechOS
  • Turn these numbers into a client-ready quote
  • Job cards, invoicing & inventory in one place
  • Works offline in the field, syncs when you’re back